Upp í vindinn - 01.05.2009, Side 37

Upp í vindinn - 01.05.2009, Side 37
Evaluating the fire safety performance In order to check the safety in a conservative way, it is necessary to simulate cases when fire safety devices fail or unexpected problems occur. Statistics show that smoke exhaust systems fail to start and to work properly in roughly 20 % of cases. In addition, it often happens that one emergency exit door remains closed. Therefore, the combination of these 2 failures remains a likely scenario which will be simulated. Results from fire simulation As discussed earlier, the main concern for evacuation purposes is the visibility. It is important that it remains above Vrit at z = 2 meters from the floor. In addition, the visibility is also checked at the height of 6 meters for the people standing at the top of the stands. Figure 2 (left) shows the visibility in a cross section containing the fire. It shows a very clear two-layer condition, with fresh air close to the floor and hot smoke above.The visibility remains acceptable after 10 minutes at ground fioor level, but is under critical value at the top of the stand. Figure 2 (right) shows a top view of the visibility at z = 2 meters from the floor shown after 12 minutes. At this time, the visibility is poor mainly on the left side and above the stand. In addition to visibility slices, visibility probes are positioned in the center of the hall and above the stand. They give the time evolution of the visibility at certain heights (see Figure 3), allowing the determination of the time when the visibility becomes critical at z = 2 m and z= 6 m above the floor, shown in Table 1. The visibility is also calculated in the case the smoke exhaust system fails to start and vents do not open. As shown by these results, the visibility becomes critical after 12:30° minutes on the ground floor and after 5:30° minutes at the top of the stands, when the smoke exhaustion system works properly. When the vents remain closed, these critical times fall to 8:30° and Figure 3:Time evolution of the visibility at the center with and without smoke exhaustion system working. 4:40° minutes respectively. Evacuation simulation The fire and smoke spread simulation has allowed the determination of the critical times, when complete evacuation must be achieved. The owner wishes to accept 3500 people on the skating ring (zone 1) and 600 on the first t„i,(min.) Probe position [Visibility <10 m] c E z = 2m,middleofhall 12:30° 01 r- > >< z = 6m, above stand 5:30° 1/1 o P z = 2m,middleofhall 8:30° z S z = 6m, above stand 4:40° Table 1 :Time to critical visibility floor (zone 2). Characteristics of the occupants, such as walking velocity, size and agility are set to be consistent with a young population from 20 to 35 years, who are most likely to attend a rock concert. The time to be aware of the fire t is estimated aw to be 50 sec. and the reaction time t to be 50 reac sec. Therefore, a total response time will be t ' r resp = t + t = 100 sec. aw reac The safety can be assessed by considering the K safe t evac Figure 1: FDS model of Skautahöllin (left). Fire and smoke visualization after 3 minutes (right). factor K ,, defined as the ratio between the evacuation time and the critical time: If K r < 1, the safety level is not sufficient. If Ksafc > 1, the safety level is sufficient. However, it is necessary to consider a certain security delay to take into account unexpected problems such as panic or longer reaction time, and how familiar the occupants are with ... upp í vindinn I 37

x

Upp í vindinn

Direkte link

Hvis du vil linke til denne avis/magasin, skal du bruge disse links:

Link til denne avis/magasin: Upp í vindinn
https://timarit.is/publication/1929

Link til dette eksemplar:

Link til denne side:

Link til denne artikel:

Venligst ikke link direkte til billeder eller PDfs på Timarit.is, da sådanne webadresser kan ændres uden advarsel. Brug venligst de angivne webadresser for at linke til sitet.